Installation Type - Genset Undermount |
Model | PWUG15 | FWUG15 |
Prime Power (kw) | 15 |
Rated Voltage (V) | 460 |
Rated Frequency (Hz) | 60 |
Dimension | L (mm) | 1316 |
W (mm) | 1550 |
H (mm) | 800 |
Weight (kg) | 705 |
Diesel Engine | Model | 404D-22(EPA/EU IIIA) | 404D-24G3 |
Manufacturer | Perkins | FORWIN |
Type | Direct-injection,4-stroke,4-cylinder, water-cooled, diesel engine |
Cylinder Number | 4 | 4 |
Cylinder Diameter (mm) | 84 | 87 |
Intake Stroke (mm) | 100 | 103 |
Maximum Power (kw) | 24.5 | 24.2 |
Displacement (L) | 2.216 | 2.45 |
Rotation (r/min) | 1800 | 1800 |
Coolant Capacity (L) | 7 | 7.8 |
Lubricating Oil Capacity (L) | 10.6 | 9.5 |
Fuel Capacity(L) | 189 |
Fuel Consumption (L/H) | 1.5∽2.5 |
Air Filter Mode | Heavy Oil-immersed Type |
Start System | Electric Start DC12V |
Auxiliary Device of Cold Start | Air Heater DC12V |
Charging Dynamo | with DC12V |
Alternator | Model | RF-15 |
Insulation Grade | F/H |
Exciting mode | Brushless Excitation |
Control System | Control System Model | PCC1420 |
Parameter Display | Generator Set:Voltage V, Current A, Frequency HZ, Active Power KW, Apparent Power KVA,Power Factor Cos∮, Cumulative Power of Generator Set KWH; Engine:Coolant Temperature, Lubrication Pressure, Rotation,Working hours,Battery Voltage, Fuel Level ect. |
Safety Protection | Generator Protection:Overvoltage / undervoltage, over frequency / under frequency, overload, short circuit. Engine Protection:Low Oil Pressure, High Water Temperature, Low Fuel Level, Charging Failure, Over Speed |
Optional Function | 1.Energy Saving via Frequency Conversion ;2.Automatic Start and Stop System. |
Auxiliary System | Battery | 12VDC-100AH Free Maintenance Battery |
Power Outlet | ISO Standard Junction Box 、Meet the Standard of CEE-17 ,32 A,It is the pointer at 3’s clock when connect the grounding pole. |
Fuel Level Gauge | Mechanical Fuel Level Gauge |
Quality Assessment System | ISO9001:2000 |
Safety Certificate | CE |